Enhancing Generator Loss of Excitation Protection with Offset Distance Relay in the Presence of STATCOM

In the realm of synchronous generators, safeguarding against the Loss of Excitation (LOE) stands as a pivotal safety measure. The repercussions of LOE extend beyond the generator itself, affecting both the generator and the interconnected electricity grid. This study delves into the use of impedance-based positive and negative offset mho relays for prompt identification of LOE phenomena. Notably, challenges arise when implementing these protection measures in the presence of Flexible AC Transmission Systems (FACTS) components, necessitating precise adjustment of relay parameters for optimal functionality. Fluctuations in the system's total impedance can lead to overreach or underreach by the relays, potentially compromising the protection mechanism. This article provides a comprehensive exploration of both types of mho relays, elucidating their configurations and drawing comparisons. The impact of STATCOM on the LOE protection of POMR and NOMR is simulated using Simulink/MATLAB. In conclusion, the essay discusses the merits and demerits of each relay strategy, shedding light on their respective advantages and limitations in the context of LOE protection. Major Findings: STATCOM presence affects generator LOE protection. Positive offset mho relays perform better. Accurate relay settings with STATCOM ratings are vital. P-Q and R-X directional methods outperform traditional G-B or U-I schemes.