Capacitive Coupling Phenomena in Gas-Insulated Switchgear Disconnectors during Impulse Voltage Tests

Gas-Insulated Substation (GIS) equipment has become increasingly significant due to its numerous advantages over con ventional Air-Insulated Substations (AIS). These advantages include compact size, higher reliability, enhanced safety, superior dielectric performance, and reduced maintenance requirements. Such benefits make GIS suitable for urban areas and challenging environmental conditions where space and operational constraints are critical. Dielectric-type tests play a crucial role in ensuring GIS equipment’s reliability and operational safety by validating its insulation’s ability to withstand both impulse overvoltages, typically caused by lightning, and temporary power frequency overvoltages arising from switching operations or system disturbances. This study focuses on lightning impulse testing of a GIS disconnector switch across an open isolating distance, emphasising the challenges encountered in achieving compliance with the requirements specified in IEC 60060-1:2010. Key challenges include managing capacitive coupling effects, voltage drop mitigation, and maintaining waveform fidelity during the test. For testing the isolating distance of a 245 kV GIS disconnector, a method is presented to address the effective voltage drop observed during lightning impulse voltage tests. This method involves a combined approach utilizing high-voltage DC as a complementary voltage source without the requirement of synchronizing equipment and ensuring the required test voltage without much voltage drop across the isolating contacts of the GIS disconnector.