Assessment of HC-290 Charge Reduction in Split Type Air Conditioner
Global warming is at the forefront to drive and develop method or equipment to avoid climate change. Kyoto protocol guides air conditioning sector to avoid use of HFCs by adopting an alternative refrigerant. HC-290, a potential alternative refrigerant, possesses negligible Ozone Depletion Potential (ODP) and a minimal Global Warming Potential (GWP). However, it is highly flammable refrigerant imposing limitation on the charge quantity that can be used in the Split Air Conditioner (SAC). Present study describes Vapor Compression Cycle (VCC) analysis for the refrigerant charge reduction by variation of some of the geometric parameters for the condenser and it also describes possible ways to reduce charge by variation to condenser without change in system process parameters of SAC. By optimizing condenser design through parametric analysis and simulation, this work explores refrigerant charge reduction in an HC-290 split air conditioner. A mathematically designed vertical tube condenser was used, and the system maintained a cooling capacity of 5100 kW and an EER of 3.85% while achieving a 24% reduction from the baseline 330g charge. The main cause of charge decrease, according to the findings, is condenser change, while expansion device sizing also affects the overall charge mass. Major Findings: By vertical tube condenser it is possible to save refrigerant charge in SAC. There is no impact on the cooling capacity and EER for the similar capacity of SAC.