Dechlorination of Mineral Insulating Oil Contaminated with Polychlorinated Biphenyls
Polychlorinated Biphenyls (PCB) were widely used as fire retardants and insulating material in the manufacture of transformers and capacitors. This was due to their ability to withstand exceptionally high temperatures. Because of their classification as a human carcinogen, the EPA banned their use in 1979, with the exception of their regulated use for a specific purpose. Transformers and Capacitors which were manufactured prior to 1979 contain oil, which may contain certain levels (ppm) of PCB. Therefore, all oil-filled equipment with PCB contamination must be disposed of. Because of their highly regulated use and disposal, all oils from transformers/power supplies need to be sampled and tested prior to disposal of the oil and the carcass. The Stockholm Convention on POPs, which was adopted in May 2001 with the objective of protecting human health and the environment from POPs, came into force on 17th May 2004. Accordingly, those mineral insulating oils which are contaminated by PCB due to retro-filling need to be treated by the PCB dechlorination procedure. This paper presents a case study of PCB dechlorination of mineral insulating oil. In this study, the dechlorination of about 65 kL of PCB-contaminated mineral insulating oil was carried out using the sodium dispersion method. After the dechlorination process, the PCB contamination levels have been decreased from 21.06 mg/kg to less than 2 mg/kg, which is the requirement as per IS 335:2018. It was recommended to reclaim or reuse the dechlorinated oil.