A Comparative Assessment of Steady-State Thermal Ampacity for Mixed-Voltage Cable Crossings: IEC 60287-3-3 Versus FEA-based 3D Modelling
Mixed-voltage underground cable corridors frequently require crossings between high-voltage and medium-voltage circuits, where localized thermal interaction can influence allowable ampacity and long-term insulation performance. Analytical approaches for crossing assessment are widely used due to their simplicity and consistency with established current rating standards. However, the availability of finite element–based three-dimensional thermal modelling enables explicit representation of spatial heat transfer in complex installation geometries. This paper presents a comparative assessment of thermal ampacity predictions for a mixed-voltage cable crossing using an analytical method based on standard current rating formulations and a finite element–based steady-state model, both implemented in CYMCAP 9.1. Perpendicular and oblique crossing configurations are evaluated to investigate the influence of crossing angle on predicted ampacity. The study provides a structured comparison of analytical and three-dimensional modelling approaches for steady-state thermal assessment of mixed-voltage cable crossings.