Estimation of Induced Overvoltage of Power Cables – A FEM Approach
Power cables are vital elements in the power system distribution network. The design of power cables with ratings above 6kV requires a metallic screen in their construction. The metallic screen represents the grounding element for the power cables. The metallic screen/sheath provides a path for the fault current to flow and be grounded. The method of bonding or grounding the metallic screen is important in the installation of power cables. Three types of bonding methods are popularly employed in the system. They are single-point, solid, and cross-bonding. The metallic screen experiences induced voltage due to the load current in the conductor in single-point bonding. The characteristics of the system determine the suitable bonding method, as each method has its own merits and demerits. The bonding and grounding method significantly affects power cable losses due to sheath-induced voltages and circulating currents. Sheath Voltage Limiters (SVL) are employed in single-pointbonded cables to limit transient overvoltages and protect the sheath. The design of the SVL also depends on the induced voltage in the system. The SVL is designed with a protective level higher than the normal induced voltage. Therefore, it does not conduct under normal load conditions. Hence, estimating the induced voltage during normal operation is essential for SVL design. This paper presents various methodologies, such as Analytical, Simulink, IEC 60287 and Finite Element Method (FEM), for estimating sheath-induced voltage, supported by a detailed case study of single-point bonding and a comparative analysis of the obtained results.