Interoperable Line Differential Protection using IEC61850
This paper provides a comprehensive overview of the state-of-theart interoperable digital line differential protection technology with the help of IEC61850, particularly Sampled Values (SV) and Generic Object-Oriented Substation Event (GOOSE) services, offering a highly flexible, interoperable, and robust communication infrastructure that can overcome challenges of interoperability limitations within C37.94. The challenges in transferring the sample values between substations are now addressed, which opens the gate to exchanging data in GOOSE and SV between substations. This paper describes the test setup and performance of two-terminal differential relays from the same vendor which is communicating in IEC61850 for transferring analog and digital signals via a Multiprotocol Label Switching – Transport Profile (MPLSTP) network to perform line differential protection. It also proposes the modelling of multi-vendor line differential protection.